TECHNICAL INFO: SANS 10087-1:2013 |
|
LOCATION OF CONTAINERS |
GENERAL |
The installation of a container(s), complete with all associated equipment and appliances and any subsequent repair or modifications to the installation, shall be carried out by a registered installer qualified to the appropriate grade (domestic or commercial grade) |
NOTE: THIS REQUIREMENT DOES NOT INCLUDE THE REPLACEMENT OF CONTAINERS |
Each container shall be located in an upright position with the valve uppermost, and shall be so placed on a solid non-combustible level base that there can be no danger of the container tilting or falling over. Compacted soil shall not be acceptable |
CONTAINERS SHALL BE SO LOCATED IN AN ACCESSIBLE POSITION THAT: |
a) full and empty containers can be changed easily; |
b) they can be disconnected and removed quickly in case of an emergency, and |
c) the container valve can be easily operated |
IN THE SELECTION OF A LOCATION OF CONTAINERS, THE FOLLOWING LOCATIONS SHALL BE AVOIDED: |
a) any position in which the containers are likely to cause obstruction, to become damaged or to be exposed to conditions likely to affect their safety; |
b) any position that is subject to extreme temperature (excluding natural elements) |
c) any position near corrosive or readily combustible substances; and |
d) any position adjacent to cellars, drains, hollows, etc, where escaping gas might collect |
INDOOR LOCATION |
Where LPG containers are permanently installed or stored in a building, the type of building (in accordance with SANS 10400-A) and the corresponding size of the container(s) shall be as follows: |
a) flats (H3): a maximum of 9 kg per flat; |
b) houses (including cluster housing and group housing (not exceeding two storeys)): a total maximum of 19 kg per unit; |
c) commercial premises (all occupancies not mentioned in this part of SANS 10087): a total maximum of 19kg per unit, provided that there is a separating element that complies with the requirements of SANS 10400-T; |
d) industrial premises (class of occupancy D1 to D4): a maximum of 19 kg per 600 m3 of building space with a total maximum of 100 kg; and |
e) for special events: consult the local fire authority concerned; and |
f) no fixed installation shall be installed inside a garage |